Inspection Status: Correction Required
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
| Date |
Description |
Inspector |
Results |
Comments |
| 10/27/1997 |
EXCAVATION/LAYOUT REBAR & ZON |
|
Correction Required |
ADDTL COMMS - 1. THERE IS NO PLANS SHOWING WHICH RETAIN WALL GOES WHERE. 2. DRAWING D-4 SHOWS YOU NEED A STEP FTG W/2 BARS @ 12 OC IN FTG. 3. GENERAL STRUCT NOTES: 3-D.1 CONCRETE & REINFORCING STEEL, CALL FOR 3 CLEARANCE WHERE CONCRETE IS PLACED DIRECTLY AGAINST EARTH. 2ND TIME THIS INSPECTION. |
| 10/27/1997 |
EXCAVATION/LAYOUT REBAR & ZON |
|
Denied |
DENIED |
| 10/20/1997 |
EXCAVATION/LAYOUT REBAR & ZON |
|
Denied |
BOTTOM OF FTG NOTSTEPPED |