Permit: T22OT00368

Parcel: 117121930

Inspection Status: Passed

Inspection History: COT - ENGR - Signage Final

Permit Number - T22OT00368

Inspection Description - COT - ENGR - Signage Final

Inspection Status - Passed

Date Description Inspector Results Comments
07/06/2022 COT - ENGR - Signage Final Hthrall Approved Entered by HTHRALL1 - Sent contractor remainder email on 7/6/22 to: Have engineer fill out special inspection form and return (field welds) Pay permit fees online Once those are done, the sign permit can be issued. Reminded contractor also to contact Daniel Urbina to obtain a right of way permit for the install.
06/28/2022 COT - ENGR - Signage Final Hthrall Approved Entered by HTHRALL1 - Resubmitted items 6/23 and reviewed 6/24 - (engineering approved) RE: sign review For: undercanopy sign AT: Hexagon / 40 E Congress for J Kaiser Sign permit: T22OT00368 Resubmittal 6/24 Reviewer: H. Thrall Codes: Unified Development Code (UDC 7A Sign Standards), National Electrical Code (NEC 600), Tucson Pima County Outdoor Lighting Code (OLC) and International Building Code (IBC) 2018 1. IBC a. appears on site welds, clarify in notes and understand that on site welds require a special inspection. Have the engineer fill out this form to be returned to staff with the name of the qualified special inspector: https://www.tucsonaz.gov/files/pdsd/forms/Special_inspection_certificate.pdf Please provide revisions to Heather.Thrall@tucsonaz.gov
06/20/2022 COT - ENGR - Signage Final hthrall Continued Entered by HTHRALL1 - RE: sign review For: undercanopy sign AT: Hexagon / 40 E Congress for J Kaiser Sign permit: T22OT00368 Resubmittal 6/10 & 6/15/22 (engineering Second review 6/20/22 Reviewer: H. Thrall Codes: Unified Development Code (UDC 7A Sign Standards), National Electrical Code (NEC 600), Tucson Pima County Outdoor Lighting Code (OLC) and International Building Code (IBC) 2018 1. UDC: a. (Not addressed) Sign needs to be shown on a precise location plan because it is in the right of way under a building canopy. Use the development plan sheet that was used for the Hexagon projecting sign. Show the precise location of the sign in relation to the building features and the property line. b. Note that this sign will need a Temporary Revocable Easement (TRE) for placement in the right of way, separate from the building canopy and the TRE for it. (Staff has confirmed the number will be case 2022-005B, once sign location noted on the development plan sheet.) c. (Not addressed) list property line frontage for the site and the suite frontage for this tenant on the development plan sheet to calculate total sign area. 2. IBC a. engineer indicates welds to underside of canopy. Photo of underside of canopy appears to show concrete. Provide expansion bolt data for mounts if underside of canopy is concrete finish, or provide current photos showing the underside of the canopy has been completed with metal. b. appears on site welds, clarify in notes and understand that on site welds require a special inspection. Have the engineer fill out this form to be returned to staff with the name of the qualified special inspector: https://www.tucsonaz.gov/files/pdsd/forms/Special_inspection_certificate.pdf Please provide revisions to Heather.Thrall@tucsonaz.gov
06/15/2022 COT - ENGR - Signage Final hthrall Continued Entered by HTHRALL1 - Contractor emailed engineering 6/15/22.
06/10/2022 COT - ENGR - Signage Final Hthrall Continued Entered by HTHRALL1 - Resubmittal received 6/7/22 - no engineering for the attachment in the sign package. Emailed contractor 6/10/22 requesting to have that information sent for the review. Real Estate Division has provided TRE number 2022-005B for the sign to aerially enroach right of way under the building canopy.
05/24/2022 COT - ENGR - Signage Final hthrall Continued Entered by HTHRALL1 - RE: sign review For: undercanopy sign AT: Hexagon / 40 E Congress for J Kaiser Sign permit: T22OT00368 Date: 5/24/22 Reviewer: H. Thrall Codes: Unified Development Code (UDC 7A Sign Standards), National Electrical Code (NEC 600), Tucson Pima County Outdoor Lighting Code (OLC) and International Building Code (IBC) 2018 1. UDC: a. Sign needs to be shown on a precise location plan because it is in the right of way under a building canopy. Use the development plan sheet that was used for the Hexagon projecting sign. Show the precise location of the sign in relation to the building features and the property line. b. Note that this sign will need a Temporary Revocable Easement (TRE) for placement in the right of way, separate from the building canopy and the TRE for it. c. list property line frontage for the site and the suite frontage for this tenant on the development plan sheet to calculate total sign area. 2. NEC a. disconnect switch is not labeled on side diagram, please identify b. provide a lock on the disconnect switch on the sign c. provide a note that the breaker panel will be labeled for the sign 3. OLC a. provide note that the timer curfew is midnight and sign shall shut off at midnight 4. IBC a. provide engineering for the mount of this sign to the underside of this building canopy, as this is over a pedestrian use area. Engineering will be reviewed when received. b. appears on site welds, clarify in notes and understand that on site welds require a special inspection. Have the engineer fill out this form to be returned to staff with the name of the qualified special inspector: https://www.tucsonaz.gov/files/pdsd/forms/Special_inspection_certificate.pdf c. check enlarged diagram for undercanopy view - missing keynotes 9, 10, 11, on plan and 14 is referencing something else d. provide clarification on plan to label the raised letter components (i.e. appears to be 3" letters) e. provide weight of the cabinet Please provide revisions to Heather.Thrall@tucsonaz.gov
10/19/2022 COT - ENGR - Signage Final Hthrall Continued Entered by HTHRALL1 - Inspector - please do not final until special inspection form returned to staff for field welds for this under-canopy sign in right of way. Please check dimensions how far away from building wall, sign height off sidewalk, and also the vertical clearance above sidewalk to sign. Thank you. Interim TRE per John Cahill in Real Estate.