Inspection History Details
Inspection Status: Not Ready
Inspection History: COT - FCON - Alarm - Final
Permit Number - T22FC00440
Inspection Description - COT - FCON - Alarm - Final
Inspection Status - Not Ready
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/26/2022 | COT - FCON - Alarm - Final | Not Ready | ||
| 09/27/2022 | COT - FCON - Alarm - Final | jfordney | Denied | Entered by JFORDNE1 - Arrived at 12:00 noon. Nobody from Red Hawk on site. No message or contact info. Reinspection fee will be added, |
| 08/30/2022 | COT - FCON - Alarm - Final | JPEEL-DAVIS | Prior to Final Inspectn | Entered by JPEELDA1 - CONFIRM MANUAL PULL AND SMOKE ABOVE THE FACP CONFIRM ALL WIRE BELOW 7' AFF IS LOCATED IN CONDUIT CONFIRM DIALER HAS A BATTERY CONFIRM THE TRANSFORMER IS LOCATED IN A LOCKING EMCLOSURE |
| COT - FCON - Alarm - Final | Not Ready | I called the contact number and no one returned my call. | ||
| 12/27/2022 | COT - FCON - Alarm - Final | Passed |