Permit: T22FC00251

Parcel: 13707047A


Addresses:

101 W IRVINGTON RD


Inspection Status: Not Ready

Inspection History: COT - FCON - Alarm - Final

Permit Number - T22FC00251

Inspection Description - COT - FCON - Alarm - Final

Inspection Status - Not Ready

Date Description Inspector Results Comments
10/26/2022 COT - FCON - Alarm - Final Not Ready
05/10/2022 COT - FCON - Alarm - Final CGates Denied Entered by CGATES1 - Smoke detector needs to be added to the FACP room.
04/06/2022 COT - FCON - Alarm - Final JPEEL-DAVIS Prior to Final Inspectn Entered by JPEELDA1 - Confirm manual pull and smoke above FACP Confirm that the tamper comes in as a Supervisory Confirm that the Starlink is not drawing power from the FACP Confirm that the Transformer is locked in a listed enclosure Confirm that the Starlink is monitoring the FACP and not through the AES.