Permit: T22FC00065

Parcel: 141210270


Addresses:

8800 E OLD VAIL RD

Inspection Status: Approved

Inspection History: FIRE SPKLR - UG, PIPING, HYDRO

Date Description Inspector Results Comments
07/20/2022 FIRE SPKLR - UG, PIPING, HYDRO Approved
03/15/2022 FIRE SPKLR - UG, PIPING, HYDRO Prior to Final Inspectn Backflow needs to be monitored before final can be given.
2. The flow still need to test the flow it needs to be 1500
02/25/2022 FIRE SPKLR - UG, PIPING, HYDRO Partial Approval Waiting on test cert and letter releasing TFD from liability
205 psi
02/23/2022 FIRE SPKLR - UG, PIPING, HYDRO Denied When I arrived on site the system had 190 psi on the guage.
We need 200psi for 2 hours.