| 08/03/2022 |
COT - ENFC - Code Enforcement - Initial |
VALDEZ |
Approved |
Entered by VALDEZ - ONSITE INSPECTION: 8-03-2022
BLDG. 1 EXTERIOR CODE VIOLATIONS
BROKEN DISCONNECTED METAL CONDUIT IRRIGATION TIMER
THERE ARE MULTIPLE JUNCTION BOXES WITH EXPOSED WIRING.
SERVICE PANELS HAVE NO LABELING OR UNREADABLE
SERVICE PANELS HAVE MISSING HARDWARE
THERE ARE MULTIPLE OVERHEAD LIGHT FIXTURES IN THE WALKWAYS WHICH ARE DAMAGED, HAZARDOUS OR NOT SERVICEABLE.
THE FOLLOWING UNITS HAVE MISSING OR BROKEN WINDOWS: 109,114 AND 115
THE BUILDING HAS MULTIPLE DOWNSPOUTS WHICH ARE NOT PROPERLY FASTENED TO THE BUILDING, MISSING COMPONENTS (SCUPPER BOXES) AND OR NOT PROPERLY SEALED
THERE ARE MULTIPLE EXTERIOR DAMAGED SCREEN DOORS.
THE BUILDING'S WALKWAYS HAVE OVERHEAD SHEETROCK WHICH IS TORN AND DAMAGED
THE EXTERIOR BUILDING'S WOOD FRAMED COLUMNS HAVE DEEP CRACKS IN THE STUCCO FINISH.
UNIT 109 IS BOARDED
UNIT 115 IS BOARDED WITH OPEN PENETRATIONS
THERE ARE MULTIPLE WINDOW MOUNTED AIR CONDITIONING UNITS WHICH ARE NOT PROPERLY SEALED OR MOUNTED.
UNIT 110 HAS A PUNCTURE IS THE WALL SHEATHING
ALL 2ND STORY STEEL GUARDS HAVE BEEN MODIFIED WITH A STEEL VERTICAL TUBING SUPPORT BOLTED TO THE CONCRETE WALKWAY AND WELDED TOP THE GUARD THE SUPPORT EXTENDS TO THE TOP BEAM BUT NOT BOLTED OR SECURED TO THE BEAM.
THE STAIRWAY GUARD HAS DAMAGED AREAS WITH BROKEN WELDS, BROKEN STEEL TUBING ALSO AREAS WITH NO GROUND SUPPORT, THERE IS ONE STEP NOT PROPERLY SUPPORTED. THE GUARD IS LOOSE IN MULTIPLE AREAS AND NOT SUPPORTED.
BLDG 2 EXTERIOR CODE VIOLATIONS
BOARDED UNITS 201,215,220,221 AND 226 WITH OPEN PENETRATIONS
UNITS WITH BROKEN WINDOWS: 201, 204, 210, 218,219, 220,221, 227,225
THERE ARE MULTIPLE OVERHEAD LIGHT FIXTURES IN THE WALKWAYS WHICH ARE DAMAGED, HAZARDOUS OR NOT SERVICEABLE.
SERVICE PANELS HAVE NO LABELING OR UNREADABLE
THE BUILDING HAS MULTIPLE DOWNSPOUTS WHICH ARE NOT PROPERLY FASTENED TO THE BUILDING, MISSING COMPONENTS (SCUPPER BOXES) AND OR NOT PROPERLY SEALED
THERE ARE MULTIPLE JUNCTION BOXES WITH EXPOSED WIRING.
THERE ARE MULTIPLE EXTERIOR DAMAGED SCREEN DOORS.
THE BUILDING'S WALKWAYS HAVE OVERHEAD SHEETROCK WHICH IS TORN AND DAMAGED
THE EXTERIOR BUILDING'S WOOD FRAMED COLUMNS HAVE DEEP CRACKS IN THE STUCCO FINISH.
THERE ARE MULTIPLE WINDOW MOUNTED AIR CONDITIONING UNITS WHICH ARE NOT PROPERLY SEALED OR MOUNTED.
ALL 2ND STORY STEEL GUARDS HAVE BEEN MODIFIED WITH A STEEL VERTICAL TUBING SUPPORT BOLTED TO THE CONCRETE WALKWAY AND WELDED TOP THE GUARD THE SUPPORT EXTENDS TO THE TOP BEAM BUT NOT BOLTED OR SECURED TO THE BEAM. THE STAIRWAY GUARD HAS DAMAGED AREAS WITH BROKEN WELDS, BROKEN STEEL TUBING ALSO AREAS OF NO GROUND SUPPORT, THE GUARD IS LOOSE IN MULTIPLE AREAS AND NOT SUPPORTED.
UNIT 223 HAS EXTERIOR WALL SHEATHING WITH GAPS
BLDG. 3 EXTERIOR CODE VIOLATIONS
THE BUILDING HAS MULTIPLE DOWNSPOUTS WHICH ARE NOT PROPERLY FASTENED TO THE BUILDING, MISSING COMPONENTS AND OR NOT PROPERLY SEALED
BOARDED UNITS 306, 305,304, 310, 311, WITH OPEN PENETRATIONS
UNITS WITH BROKEN WINDOWS: 312,
SERVICE PANELS HAVE NO LABELING OR UNREADABLE
THERE ARE MULTIPLE OVERHEAD LIGHT FIXTURES IN THE WALKWAYS WHICH ARE DAMAGED, HAZARDOUS OR NOT SERVICEABLE.
THERE ARE MULTIPLE EXTERIOR DAMAGED SCREEN DOORS.
THERE ARE MULTIPLE WINDOW MOUNTED AIR CONDITIONING UNITS WHICH ARE NOT PROPERLY SEALED OR MOUNTED.
WINDOW MOUNTED AIR-CONDITIONING UNITS SHALL HAVE APPROVED MATERIALS TO MAKE UP FOR A SEAL TIGHT INSTALL, CARDBOARD, UNPROTECTED PLYWOOD AMD PARTICLE BOARD ARE NOT APPROVED MATERIAL
ALL STEEL GUARDS HAVE BEEN MODIFIED WITH A STEEL VERTICAL TUBING SUPPORT BOLTED TO THE CONCRETE WALKWAY AND WELDED TOP THE GUARD THE SUPPORT EXTENDS TO THE TOP BEAM BUT NOT BOLTED OR SECURED TO THE BEAM. THE STAIRWAY HAS DAMAGED AREAS WITH BROKEN WELDS, BROKEN STEEL TUBING ALSO AREAS OF NO GROUND SUPPORT, MULTIPLE AREA WITH RUSTED GUARD MEMBERS THERE ARE MULTIPLE DAMAGED CONCRETE STEPS AND ONE LOOSE STEP.. THE GUARD IS LOOSE IN MULTIPLE AREAS AND NOT SUPPORTED.
POOL AREA / DIRTY WATER WITH REFUSE INSIDE THE POOL AREA.
LAUNDRY ROOM/ STORAGE EXTERIOR CODE VIOLATIONS
THE LAUNDRY ROOM IS CONDEMNED
THE EXTERIOR ELECTRICAL PANEL HAS A UTILITY COVER WHICH IS NOT COMPATIBLE WITH THE MAIN DISCONNECT.
THERE IS A FLEX CONDUIT WHICH RUNS TO THE SHED. NO PERMIT FOR THE INSTALL
OPEN OUTLET NO PROTECTIVE COVER OVER DUPLEX RECEPTACLE
STORAGE ROOM BOARDED
SHEETROCK DAMAGE TO STORAGE ROOM
BLDG. 4 EXTERIOR CODE VIOLATIONS
THE BUILDING HAS MULTIPLE DOWNSPOUTS WHICH ARE NOT PROPERLY FASTENED TO THE BUILDING, MISSING COMPONENTS AND OR NOT PROPERLY SEALED
BOARDED UNITS 410, WITH OPEN PENETRATIONS
UNITS WITH BROKEN WINDOWS: 411, 410,401,403, 402,405
UNIT 405 CONDENSATE LEAKAGE FROM THE WINDOW MOUNTED AIR CONDITIONING UNIT IS CAUSING DAMAGE TO THE BUILDINGS WOOD BEAM LOCATED AT THE STAIRWELL. WOOD ROT.
UNIT 402 THERE ARE CRACKS CONCRETE WALKWAY.
SERVICE PANELS HAVE NO LABELING OR UNREADABLE
THERE ARE MULTIPLE OVERHEAD LIGHT FIXTURES IN THE WALKWAYS WHICH ARE DAMAGED, HAZARDOUS OR NOT SERVICEABLE.
THERE ARE MULTIPLE EXTERIOR DAMAGED SCREEN DOORS.
THERE ARE MULTIPLE WINDOW MOUNTED AIR CONDITIONING UNITS WHICH ARE NOT PROPERLY SEALED OR MOUNTED.
WINDOW MOUNTED AIR-CONDITIONING UNITS SHALL HAVE APPROVED MATERIALS TO MAKE UP FOR A SEAL TIGHT INSTALL, CARDBOARD, UNPROTECTED PLYWOOD AMD PARTICLE BOARD ARE NOT APPROVED MATERIAL
THERE ARE MULTIPLE OVERHEAD LIGHT FIXTURES IN THE WALKWAYS WHICH ARE DAMAGED, HAZARDOUS OR NOT SERVICEABLE. THERE ARE UNAPPROVED WRING METHODS FROM THE WALKWAYS LIGHTS WHICH FEED EXTERIOR BUILDING LIGHT FIXTURES.
ALL STEEL GUARDS HAVE BEEN MODIFIED WITH A STEEL VERTICAL TUBING SUPPORT BOLTED TO THE CONCRETE WALKWAY AND WELDED TOP THE GUARD THE SUPPORT EXTENDS TO THE TOP BEAM BUT NOT BOLTED OR SECURED TO THE BEAM. THE STAIRWAY HAS DAMAGED AREAS WITH BROKEN WELDS, BROKEN STEEL TUBING ALSO AREAS OF NO GROUND SUPPORT, MULTIPLE AREA WITH RUSTED GUARD MEMBERS THERE ARE MULTIPLE DAMAGED CONCRETE STEPS AND ONE LOOSE STEP. THE GUARD IS LOOSE IN MULTIPLE AREAS AND NOT SUPPORTED.
|