Inspection History Details
Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
Case Number - T22DV04067
Inspection Description - INSP - INITIAL CODE ENFORCMENT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/19/2022 | INSP - INITIAL CODE ENFORCMENT | Approved | ON SITE REPAIRS HAVE BEEN MADE. CLEARANCE IS NOW AT CODES MINIMUM 10 FT HEIGHT. | |
07/20/2022 | INSP - INITIAL CODE ENFORCMENT | Approved | ON SITE WITH INSPECTOR VALDEZ FOUND IMPROPER HEIGHT FEEDERS BETWEEN TWO 1 LEVEL APARTMENT BUILDINGS THAT WERE LOCATED OVER THE COURTYARD AND SIDEWALK AREAS. | |
07/19/2022 | INSP - INITIAL CODE ENFORCMENT | Approved | ONSITE INSPECTION: THE OVERHEAD FEEDERS FROM THE EAST BUILDING TO THE CENTER BUILDING HAVE 8 FEET OF GROUND CLEARANCE. CODE REQUIRES 10 FEET THE ROOF MAST SUPPORT IS BENT. |