Case: T22DV01482

Parcel: 138144510

Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Case Number - T22DV01482

Inspection Description - INSP - INITIAL CODE ENFORCMENT

Inspection Status - Approved

Date Description Inspector Results Comments
02/25/2022 INSP - INITIAL CODE ENFORCMENT Approved UNIT 6103 HAS ENDURED WATER INTRUSION FROM THE FIRE THAT OCCURRED AT THE UNIT ABOVE. THERE IS WATER COMING OUT OF THE WALL CELLS THAT HAVE ENERGIZED ELECTRICAL DEVICES AND CONDUCTORS THROUGHOUT THE APARTMENT UNIT.

ELECTRICAL: ALL ELECTRICAL DEVICES NEED TO BE EVALUATED OR REPLACED BY A LICENSE CONTRACTOR. T.E.P. HAS BOOTED THE METER TO DEACTIVATE THE WET DEVICES.

PLUMBING: WATER HEATER WITH A MANUFACTURE DATE OF 2016 HAS BEEN INSTALLED WITHOUT A PERMIT IN A NON-CODE COMPLIANT MANNER.

MECHANICAL: HVAC SYSTEM HAS BEEN INSTALLED WITHOUT PERMITS IN A NON-CODE COMPLAINT AND HAZARDOUS MANNER. ITS DEDICATED DISCONNECT IS OBSTRUCTED FROM BEING ABLE TO BE TERMINATED, ITS CONDUCTORS ARE NOT PROPERLY ANCHORED AND IS SUSPENDED BY THE CONDUIT.

UNIT HAS BEEN POSTED UNFIT TO OCCUPY UNTIL ALL PROPER PERMITS ARE OBTAINED FOR THE RESTORATION. PROPERTY MANAGER IS AWARE OF VIOLATIONS AND THE NEED TO OBTAIN PERMITS. PROPERTY MAINTENANCE HAS SECURED THE UNIT.