Inspection History Details
Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/29/2022 | INSP - INITIAL CODE ENFORCMENT | Approved | EMERGENCY CAL OUT BY TFD: THERE WAS AN EXTERIOR FIRE TO THE BAILS OF CARDBOARD REAR OF THE STORE. THERE IS MILD DISCOLORATION THE AN AREA OF 4 BY 6 FOOT OF BUILDINGS CMU BLOCK NEXT TO THE MAIN ELECTRICAL SERVICE. ELECTRICAL: FIRE DAMAGE TO THE MAIN SERVICE AND ALL INTERNAL COMPONENTS, FEEDERS, CONDUCT ARE BURNT. THE CABINET HAS MAJOR DAMAGE WITH A BENT DOOR. THE SERVICE ENTRANCE CABINET DOOR HAS HEAT DAMAGE, THE CONDUIT SEALS INSIDE THE CABINET HAVE HEAT DAMAGE. THE SERVICE ENTRANCE FEEDERS INSIDE THE CURRENT TRANSFORMER CABINET HAS SOME FOREIGN RESIDUE. TEP DID DISCONNECT POWER AT THE TRANSFORMER. PLUMBING: N/A MECHANICAL: N/A REMARKS: THE DOLLAR TREE STORE WAS CONDEMNED, UNFIT TO OCCUPY. PERMITS ARE REQUIRED FOR THE REPLACEMENT OF THE MAIN SERVICE AND CONDUIT. THE CURRENT TRANSFORMER AND SERVICE ENTRANCE EQUIPMENT AND ALL FEEDERS. SHALL BE EVALUATED FOR SERVICEABLY BY AN ELECTRICAL ENGINEER. |