Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T22DV00786

Parcel: 11007414F


Addresses:

3927 E GRANT RD


Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Case Number - T22DV00786

Inspection Description - INSP - INITIAL CODE ENFORCMENT

Inspection Status - Approved

Date Description Inspector Results Comments
01/29/2022 INSP - INITIAL CODE ENFORCMENT Approved EMERGENCY CAL OUT BY TFD: THERE WAS AN EXTERIOR FIRE TO THE BAILS OF CARDBOARD REAR OF THE STORE. THERE IS MILD DISCOLORATION THE AN AREA OF 4 BY 6 FOOT OF BUILDINGS CMU BLOCK NEXT TO THE MAIN ELECTRICAL SERVICE.

ELECTRICAL: FIRE DAMAGE TO THE MAIN SERVICE AND ALL INTERNAL COMPONENTS, FEEDERS, CONDUCT ARE BURNT. THE CABINET HAS MAJOR DAMAGE WITH A BENT DOOR.
THE SERVICE ENTRANCE CABINET DOOR HAS HEAT DAMAGE, THE CONDUIT SEALS INSIDE THE CABINET HAVE HEAT DAMAGE. THE SERVICE ENTRANCE FEEDERS INSIDE THE CURRENT TRANSFORMER CABINET HAS SOME FOREIGN RESIDUE. TEP DID DISCONNECT POWER AT THE TRANSFORMER.

PLUMBING: N/A


MECHANICAL: N/A


REMARKS: THE DOLLAR TREE STORE WAS CONDEMNED, UNFIT TO OCCUPY. PERMITS ARE REQUIRED FOR THE REPLACEMENT OF THE MAIN SERVICE AND CONDUIT.
THE CURRENT TRANSFORMER AND SERVICE ENTRANCE EQUIPMENT AND ALL FEEDERS. SHALL BE EVALUATED FOR SERVICEABLY BY AN ELECTRICAL ENGINEER.