Case: T22DV00626

Parcel: 128100810

Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Date Description Inspector Results Comments
01/24/2022 INSP - INITIAL CODE ENFORCMENT Approved EMERGENCY CALL OUT BY TFD: THERE IS DAMAGE TO THE EXTERIOR WOOD DOOR AND THE CUT OFF COMPARTMENT DIMENSIONED AT 3 X 1 FOOT. THE INTERIOR ΒΌ INCH PANEL BOARD IS BURNT THE PANEL BOARD WAS THE BARRIER BETWEEN THE COMPARTMENT AND THE WASH ROOM, THE DAMAGED BOARD IS ESTIMATED AT 3 FEET WIDE BY 7 FEET IN HEIGHT, THERE IS A SMALL PUNCTURE IN THE BOARD, THE FRAMED WOOD MEMBERS TO THE DOOR ARE ALSO DAMAGED.

ELECTRICAL: THE COMPARTMENT HAS JUNCTION BOXES AND WIRING BURNT AND BARE.
THE WASH ROOM HAS A TWO OVERHEAD LIGHT FIXTURES, ONE SWITCH, AN OUTLET WITH DUPLEX RECEPTACLE AND A 225 AMP PANEL WHICH ARE WET FROM THE FIRE FIGHTERS. TEP LOCKED OUT THE UNIT 260 DISCONNECT WITH PAD LOCK.

PLUMBING: THE COMPARTMENT HAS WATER SUPPLY COPPER PIPING WITH 2 BALL VALVE IN THE OFF POSITION. THE SPRINKLER SYSTEM DID NOT DISCHARGE.


MECHANICAL: MILD SMOKE IN THE INTERIOR


REMARKS: THE UNIT WAS CONDEMNED, UNFIT TO OCCUPY. PERMITS ARE REQUIRED FOR THE WATER / FIRE DAMAGE.