Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Not Ready
Inspection History: COT - LCPL - Plumbing Intermediate
Permit Number - T22CM08079
Inspection Description - COT - LCPL - Plumbing Intermediate
Inspection Status - Not Ready
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/27/2022 | COT - LCPL - Plumbing Intermediate | Not Ready | ||
COT - LCPL - Plumbing Intermediate | Re-inspection required | 5/30/23: Nail plate needed at electrical wiring in garage, top plate penetration must be sealed, back porch light covered by lath, seal all penetrations going through bottom floor to second floor, nail plates missing through the house, seal all penetrations through vapor barrier, incorrect plate at ABS in stair way, in laundry room wires at light switch has to be made up and secured, seal penetration in laundry room bottom plate, secure receptacle box in upstairs room and bathroom, secure thermostat wire to wall, dry vents, tubs are not tested for leakage, STOPPED INSPECTION MORE ITEMS MAY BE ADDED. | ||
05/31/2023 | COT - LCPL - Plumbing Intermediate | Re-inspection required | corrections not complete. | |
06/01/2023 | COT - LCPL - Plumbing Intermediate | Passed |