Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSEL - Electrical Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/04/2024 | COT - RSEL - Electrical Final | Re-inspection required | 10/4/24: arc fault protected breakers for the bedroom is required. Main panel needs breakers labeled. Exterior receptacle needs weather cover and needs to be weather resistant. Smoke detector required outside of master bedroom. | |
| 12/05/2024 | COT - RSEL - Electrical Final | Passed | 10/4/24: arc fault protected breakers for the bedroom is required. Main panel needs breakers labeled. Exterior receptacle needs weather cover and needs to be weather resistant. Smoke detector required outside of master bedroom. 12/5/24: corrections made ok to issue letter of completion |