Inspection Status: Re-inspection required
Inspection History: RSBU - Building Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/04/2024 | RSBU - Building Final | Re-inspection required | 10/4/24: arc fault protected breakers for the bedroom is required. Main panel needs breakers labeled. Exterior receptacle needs weather cover and needs to be weather resistant. Smoke detector required outside of master bedroom. | |
| 12/05/2024 | RSBU - Building Final | Passed | 10/4/24: arc fault protected breakers for the bedroom is required. Main panel needs breakers labeled. Exterior receptacle needs weather cover and needs to be weather resistant. Smoke detector required outside of master bedroom. 12/5/24: corrections made ok to issue letter of completion |