Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Inspection Status: Not Ready

Inspection History: COT - LCPL - Plumbing Intermediate 

Date Description Inspector Results Comments
10/27/2022 COT - LCPL - Plumbing Intermediate  Not Ready
03/30/2023 COT - LCPL - Plumbing Intermediate  Re-inspection required March 30th: approved plans not on site, maintain min 1" clearance around B-vent to combustibles, maintain min 10 feet from fresh air intake to vents, support flex duct off sprinkler pipe thru-out, fire block top of mechanical chase, vertical fire blocking can not exceed 10 feet, smoke det is within 3 feet of register
08/22/2023 COT - LCPL - Plumbing Intermediate  Re-inspection required
08/24/2023 COT - LCPL - Plumbing Intermediate  Passed