Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSME - Mechanical Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/01/2025 | COT - RSME - Mechanical Final | Re-inspection required | 10/1/25 1. Laundry receptacles not on GFCI 2. Water hammer arrestors needed at laundry, dishwasher, ice maker. 3. No power at dishwasher/garbage disposal receptacle. 4. Laundry receptacles in master laundry have open ground and need to be GFCI protected. 5. Master bathroom electrical, incomplete. 6. Pool bathroom receptacles have no power. 7. Guest house locked. 8. Main panel needs all breakers label properly and in ink. Currently they are marked in pencil on the panel. |
|
| 10/08/2025 | COT - RSME - Mechanical Final | Not Ready | Add angle stops at all bathroom lavs. Add separate circuit at kitchens. Minimum of two. Provide proper clearances for disconnects in mechanical rooms. Provide gfci receptacles in mechanical rooms. Provide 3” clearance from earth for a/c units. Outdoor shower needs to be completed. Termination of UF cable along with water line to new fountain area need to be completed. Provide arc fault breakers at main panel along with permanent labeling. Both main and sub panel. 10/8/2025 |
|
| 10/28/2025 | COT - RSME - Mechanical Final | Canceled | 10-28-25: cancelled by contractor. | |
| 11/12/2025 | COT - RSME - Mechanical Final | Passed |