Permit: T22CM06918

Parcel: 131060620

Inspection Status: Not Ready

Inspection History: COT - RSBU - Exterior Clips/Sheathing 

Permit Number - T22CM06918

Inspection Description - COT - RSBU - Exterior Clips/Sheathing 

Inspection Status - Not Ready

Date Description Inspector Results Comments
10/26/2022 COT - RSBU - Exterior Clips/Sheathing  Not Ready
04/14/2023 COT - RSBU - Exterior Clips/Sheathing  Re-inspection required Anchor nut washer required to be square plate washers at shear walls SW11 and greater, shearwall edge nailing not per schedule, framing at powder room opening not per plan, block base of stair landings, base plate nailing at 2nd floor shear walls not per schedule
04/21/2023 COT - RSBU - Exterior Clips/Sheathing  Canceled 4/21/23: inspection canceled due to work load.
04/25/2023 COT - RSBU - Exterior Clips/Sheathing  Re-inspection required Anchor nut washer required to be square plate washers at shear walls SW11 and greater, shearwall edge nailing not per schedule, framing at powder room opening not per plan, block base of stair landings, base plate nailing at 2nd floor shear walls not per schedule
Renail roof
4/21/23: inspection canceled due to work load.
4/25/23: plate washers require a round washer under the anchor nut, 2nd floor shear wall base plate not nailed per schedule,2nd floor shear walls not nailed per schedule
04/27/2023 COT - RSBU - Exterior Clips/Sheathing  Passed