Inspection History Details
Inspection Status: Not Ready
Inspection History: RSBU - Building Final
Permit Number - T22CM06386
Inspection Description - RSBU - Building Final
Inspection Status - Not Ready
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/27/2022 | RSBU - Building Final | Not Ready | ||
07/18/2023 | RSBU - Building Final | Re-inspection required | Add outlet receptacle to kitchen countertop. Outlets must be within 24" of countertop edge per code E3901.4.1 of 2018 IRC. Dead front at service missing labeling for future solar use. | |
07/24/2023 | RSBU - Building Final | Passed |