Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSPL - Plumbing Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| COT - RSPL - Plumbing Final | Re-inspection required | 4/11/25 1. Dishwasher/garbage disposal are not GFCI protected. 2. Ice for fridge needs water hammer arrestor. 3. Outlet in master bedroom by the closet is very loose. 4. Bathroom 2 has open ground. 5. Laundry receptacles need to be GFCI protected. 6. Thermostat is at 60", needs to be no higher than 48" per city ordinance. 7. Exterior outlet in the front and back of house are not WR rated. 8. Paint drain line for a/c condensate to prevent heat damage. |
||
| 04/15/2025 | COT - RSPL - Plumbing Final | Passed | 4/15/2025 approved all corrections have been made. |