Inspection Status: Passed
Inspection History: COT - RSEL - Electrical Reconnect
| Date |
Description |
Inspector |
Results |
Comments |
| 09/26/2022 |
COT - RSEL - Electrical Reconnect |
TGAUSP |
Approved |
Entered by VVERA1 - Approved, please send RECN Clearance to TEP (meter #158803507) |
| 09/22/2022 |
COT - RSEL - Electrical Reconnect |
TGAUSP |
Not ready for Inspection |
Entered by NGARCIA3 - NR, still working on corrections
|
| 08/29/2022 |
COT - RSEL - Electrical Reconnect |
DQUINN |
Denied |
Entered by NGARCIA3 - de
This house is not safe to be reconnected. There are many examples of non-professional wiring existing, such as multiple runs of Romex stapled to wall exteriors with unmounted outlets, questionable old and new panels on the interior and exterior, and a possible mix of 2 wire and 3 wire feeds to 3 prong outlets.
Recommend a licensed electrician do a complete system evaluation to determine the extent of corrections needed before a reconnect will be allowed. |
| 08/23/2022 |
COT - RSEL - Electrical Reconnect |
DQUINN |
Cancelled |
Entered by VVERA1 - ca
By Larry |