Inspection History Details
Inspection Status: Not Ready
Inspection History: COT - RSBU - Exterior Clips/Sheathing
Permit Number - T22CM06125
Inspection Description - COT - RSBU - Exterior Clips/Sheathing
Inspection Status - Not Ready
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/26/2022 | COT - RSBU - Exterior Clips/Sheathing | Not Ready | ||
11/02/2022 | COT - RSBU - Exterior Clips/Sheathing | Not Ready | Missing anchor bolts behind shear wall and edges of plates. missing rsp clips on studs. the center roof support needs to be re installed. nail all edges of plates every 16”. | |
11/07/2022 | COT - RSBU - Exterior Clips/Sheathing | Not Ready | center roof needs to have supports. replace 6x4 post to support beam for stairs. needs to be continuous. | |
11/16/2022 | COT - RSBU - Exterior Clips/Sheathing | Passed | corrections were made. |