Permit: T22CM05773

Parcel: 13632002X


Addresses:

4092 S MELPOMENE WY

Inspection Status: Re-inspection required

Inspection History: COT - RSME - Mechanical Final 

Date Description Inspector Results Comments
COT - RSME - Mechanical Final  Re-inspection required 6/20/23: A/C unit missing lock caps at outside condenser, A/C Unit is being over charged ( max circuit breaker Or fuse is 35) being fed by 40Amp breaker. Secondary condensate drain needs 90 degree elbow.
06/23/2023 COT - RSME - Mechanical Final  Passed