Permit: T22CM05704

Parcel: 126040410


Addresses:

726 N ERIN AV

Inspection Status: Re-inspection required

Inspection History: COT - RSEL - Electrical Final 

Date Description Inspector Results Comments
08/04/2023 COT - RSEL - Electrical Final  Re-inspection required 2 Exterior electrical outlets are protected by a GFCI receptacle. 3 interior electrical outlets are required to be GFCI protected per code E3902.2 for storage buildings. Need to install GFCI outlets or GFCI breakers to protect these outlets. Call for re-inspection once corrected.
08/09/2023 COT - RSEL - Electrical Final  Passed 8/9/23: GFCI outlets have been installed to protect all interior storage area electrical outlets. Okay to issue Certificate of Completion.