Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Not Ready
Inspection History: RSBU - Building Final
| Date |
Description |
Inspector |
Results |
Comments |
| 10/27/2022 |
RSBU - Building Final |
|
Not Ready |
|
|
RSBU - Building Final |
|
Re-inspection required |
5/21/24: dishwasher receptacle needs to be GFCI Protected. Hammer arrestor needed for dishwasher. Max Breaker for mini split is wrong size. Condenser lines for mini split needs to be in gutter style protection. |
| 08/19/2024 |
RSBU - Building Final |
|
Passed |
|