Inspection Status: Not Ready
Inspection History: COT - RSME - Mechanical Final
| Date |
Description |
Inspector |
Results |
Comments |
| 10/27/2022 |
COT - RSME - Mechanical Final |
|
Not Ready |
|
|
COT - RSME - Mechanical Final |
|
Re-inspection required |
5/21/24: dishwasher receptacle needs to be GFCI Protected. Hammer arrestor needed for dishwasher. Max Breaker for mini split is wrong size. Condenser lines for mini split needs to be in gutter style protection. |
| 08/19/2024 |
COT - RSME - Mechanical Final |
|
Passed |
|