Inspection History Details
Inspection Status: Not Ready
Inspection History: COT - LCBU - Framing
Permit Number - T22CM05206
Inspection Description - COT - LCBU - Framing
Inspection Status - Not Ready
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/27/2022 | COT - LCBU - Framing | Not Ready | ||
| 05/04/2023 | COT - LCBU - Framing | Re-inspection required | 5/4/23: incomplete plans (missing electrical), GEC not connected to Ufer, over-notching in bearing wall studs, insulate behind the tub, nail plate romex, add smoke det outside front bedroom, over-notch non-bearing wall studs. INSPECTION STOPPED. MORE ITEMS MAY BE ADDED. | |
| 05/08/2023 | COT - LCBU - Framing | Canceled | 5/4/23: loose Ufer clamp connection, over-notch bearing wall studs, seal open chase in the garage, secure gas line in the laundry room. Sister a new stud to the fractured bearing wall stud in laundry, nail plate ABSA in the laundry, retype exhaust duct in laundry, over-spanned stud in non-bearing wall in laundry. INSPECTION STOPPED. MORE ITEMS MAY BE ADDED. 5/8/23: inspection canceled by Chris Suda |
|
| 05/09/2023 | COT - LCBU - Framing | Re-inspection required | 5/4/23: incomplete plans (missing electrical), GEC not connected to Ufer, over-notching in bearing wall studs, insulate behind the tub, nail plate romex, add smoke det outside front bedroom, over-notch non-bearing wall studs. INSPECTION STOPPED. MORE ITEMS MAY BE ADDED. 5/4/23: loose Ufer clamp connection, over-notch bearing wall studs, seal open chase in the garage, secure gas line in the laundry room. Sister a new stud to the fractured bearing wall stud in laundry, nail plate ABSA in the laundry, retype exhaust duct in laundry, over-spanned stud in non-bearing wall in laundry. INSPECTION STOPPED. MORE ITEMS MAY BE ADDED. 5/4/23: loose Ufer clamp connection, over-notch bearing wall studs, seal open chase in the garage, secure gas line in the laundry room. Sister a new stud to the fractured bearing wall stud in laundry, nail plate ABSA in the laundry, retype exhaust duct in laundry, over-spanned stud in non-bearing wall in laundry. INSPECTION STOPPED. MORE ITEMS MAY BE ADDED. 5/8/23: inspection canceled by Chris Suda 5/9/23: inspection canceled by Chris Suda |
|
| 05/17/2023 | COT - LCBU - Framing | Re-inspection required | 5/4/23: incomplete plans (missing electrical), GEC not connected to Ufer, over-notching in bearing wall studs, insulate behind the tub, nail plate romex, add smoke det outside front bedroom, over-notch non-bearing wall studs. INSPECTION STOPPED. MORE ITEMS MAY BE ADDED. 5/4/23: loose Ufer clamp connection, over-notch bearing wall studs, seal open chase in the garage, secure gas line in the laundry room. Sister a new stud to the fractured bearing wall stud in laundry, nail plate ABSA in the laundry, retype exhaust duct in laundry, over-spanned stud in non-bearing wall in laundry. INSPECTION STOPPED. MORE ITEMS MAY BE ADDED. 5/4/23: loose Ufer clamp connection, over-notch bearing wall studs, seal open chase in the garage, secure gas line in the laundry room. Sister a new stud to the fractured bearing wall stud in laundry, nail plate ABSA in the laundry, retype exhaust duct in laundry, over-spanned stud in non-bearing wall in laundry. INSPECTION STOPPED. MORE ITEMS MAY BE ADDED. 5/8/23: inspection canceled by Chris Suda 5/9/23: inspection canceled by Chris Suda 5/17/23: sister a new stud onto the broken stud behind the panel, open chase at east wall of garage, renail AC platform, condensate line traps, fire block top of chase above entrance to master bedroom, fire block all chases every 10 feet horizontally |
|
| 05/19/2023 | COT - LCBU - Framing | Passed |