Permit: T22CM05132

Parcel: 132190270


Addresses:

3014 E MICHIGAN ST


Inspection Status: Not Ready

Inspection History: COT - RSEL - Electrical Final 

Permit Number - T22CM05132

Inspection Description - COT - RSEL - Electrical Final 

Inspection Status - Not Ready

Date Description Inspector Results Comments
10/27/2022 COT - RSEL - Electrical Final  Not Ready
09/28/2022 COT - RSEL - Electrical Final  DQUINN Not ready for Inspection Entered by VVERA1 - nr Being a virtual inspection on the phone, Anna, the young lady present, did not have tools to be able to open the panel cover. The panel had indicators on the outside, that appear to show unlicensed and unprofessional workmanship and materials. The panel has been improperly cut for conduit penetration on the right side. There is no evidence of bonding and grounding for the system. There is no address label on the panel. Peripherally, there appears to be possible unsafe/unprofessional wiring as well. It is recommended that a licensed electrician evaluate the panel and distribution system, and make all appropriate repairs and replacements, for the safety of this dwelling unit and it’s inhabitants, as soon as possible, if anyone is residing there.
10/21/2022 COT - RSEL - Electrical Final  Partial Pass