Inspection History Details
Inspection Status: Passed
Inspection History: COT - RSPL - Plumbing Final
Permit Number - T22CM04995
Inspection Description - COT - RSPL - Plumbing Final
Inspection Status - Passed
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/09/2022 | COT - RSPL - Plumbing Final | TGAUSP | Approved | Entered by NGARCIA3 - Approved, PEX lines okay per PPFA installation handbook for PEX |
| 08/03/2022 | COT - RSPL - Plumbing Final | RCHANDLER | Denied | Entered by VVERA1 - Denied-1-Install hammer arrestees at ice maker and dishwasher. 2-Pex piping needs 12” minimum clearance from b vent at water heater. 3-Install nail plates at guest bathroom. 5-Secure piping at hose Bibb by guest bathroom. 6-Obtain approval of all inspections. |