Permit Number - T22CM04808
Inspection Description - COT - LCME - Kitchen Hood
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/06/2023 | COT - LCME - Kitchen Hood | Re-inspection required | 10/6/23: vertical section of grease duct was installed and double wrapped without inspection. Remove this section and have it inspected and approved by a City of Tucson inspector before reinstalling. | |
COT - LCME - Kitchen Hood | Partial Pass | 10/10/23: vertical section of grease duct passed smoke test okay to wrap and install, lower horizontal section still needs inspection | ||
10/12/2023 | COT - LCME - Kitchen Hood | Passed | 10/6/23: vertical section of grease duct was installed and double wrapped without inspection. Remove this section and have it inspected and approved by a City of Tucson inspector before reinstalling. 10/10/23: vertical section of grease duct passed smoke test okay to wrap and install, lower horizontal section still needs inspection 10/12/23: complete grease duct smoke tested and approved to wrap. |
|
10/17/2023 | COT - LCME - Kitchen Hood | Passed |