Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T22CM04567

Parcel: 13213066A

Inspection Status: Not Ready

Inspection History: RSME - Mechanical Progress 

Permit Number - T22CM04567

Inspection Description - RSME - Mechanical Progress 

Inspection Status - Not Ready

Date Description Inspector Results Comments
10/27/2022 RSME - Mechanical Progress  Not Ready
06/13/2023 RSME - Mechanical Progress  Not Ready
06/16/2023 RSME - Mechanical Progress  Canceled canceled per contractor 6/16/2023
06/20/2023 RSME - Mechanical Progress  Re-inspection required 6/20/23: no building UFER. install 2 ground rods with a continuous #4 CU GEC, block base of stair landings and water heater base, fire block AC chase on 2nd floor, provide approved plans at all inspections, attic was foam insulated without inspection.
06/26/2023 RSME - Mechanical Progress  Not Ready
07/03/2023 RSME - Mechanical Progress  Not Ready
07/06/2023 RSME - Mechanical Progress  Not Ready
07/11/2023 RSME - Mechanical Progress  Passed