Inspection History Details
Inspection Status: Not Ready
Inspection History: COT - RSEL - Electrical Final
Permit Number - T22CM04442
Inspection Description - COT - RSEL - Electrical Final
Inspection Status - Not Ready
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/27/2022 | COT - RSEL - Electrical Final | Not Ready | ||
06/20/2023 | COT - RSEL - Electrical Final | Re-inspection required | 6/20/23: missing light bulbs at outdoor lights, water hose bib missing foam insulation and uv rated tape, electrical panel missing labeling for future solar use as per 2018 IRC code T103.9, refrigerant line for a/c not wrapped with uv rated tape, thermostat must be placed no higher than 54" OC above the floor per plans, provide ladder for attic access. | |
06/22/2023 | COT - RSEL - Electrical Final | Passed |