Permit: T22CM04442

Parcel: 141433560

Inspection Status: Not Ready

Inspection History: COT - RSPL - Plumbing Final 

Permit Number - T22CM04442

Inspection Description - COT - RSPL - Plumbing Final 

Inspection Status - Not Ready

Date Description Inspector Results Comments
10/27/2022 COT - RSPL - Plumbing Final  Not Ready
06/14/2022 COT - RSPL - Plumbing Final  RPARSON1 Prior to Final Inspectn Entered by RPARSON1 - NO FINAL UNTIL THE PUBLIC SEWER G-2020- 059/P21WP00060, G-20-089/P21WP00061 AND THE DOWNSTREAM OFFSITE PUBLIC SEWER FOR PARCEL 4 G-2020-087 IS ACCEPTED AND RELEASED BY PCRWRD
04/03/2023 COT - RSPL - Plumbing Final  Not Ready Not ready for final inspection.
05/17/2023 COT - RSPL - Plumbing Final  Not Ready
06/20/2023 COT - RSPL - Plumbing Final  Re-inspection required 6/20/23: missing light bulbs at outdoor lights, water hose bib missing foam insulation and uv rated tape, electrical panel missing labeling for future solar use as per 2018 IRC code T103.9, refrigerant line for a/c not wrapped with uv rated tape, thermostat must be placed no higher than 54" OC above the floor per plans, provide ladder for attic access.
06/22/2023 COT - RSPL - Plumbing Final  Passed