Inspection History Details
Inspection Status: Not Ready
Inspection History: COT - LCEL - Electrical Above Ceiling
Permit Number - T22CM04242
Inspection Description - COT - LCEL - Electrical Above Ceiling
Inspection Status - Not Ready
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/26/2022 | COT - LCEL - Electrical Above Ceiling | Not Ready | ||
03/08/2023 | COT - LCEL - Electrical Above Ceiling | Re-inspection required | Fill & seal holes in metal hard duct, support flex duct off grid, open j-boxes, support all electric whips off grid. | |
03/09/2023 | COT - LCEL - Electrical Above Ceiling | Re-inspection required | Fill & seal holes in metal hard duct, support flex duct off grid, open j-boxes, support all electric whips off grid. March 9th: ceiling tiles are being installed before above ceiling inspection has been approved. |
|
03/10/2023 | COT - LCEL - Electrical Above Ceiling | Re-inspection required | Fill & seal holes in metal hard duct, support flex duct off grid, open j-boxes, support all electric whips off grid. March 9th: ceiling tiles are being installed before above ceiling inspection has been approved. March 10th: open j-boxes, circuits not in conduit to roof, holes in duct, whips on grid, tiles obstructing the inspection |
|
03/13/2023 | COT - LCEL - Electrical Above Ceiling | Partial Pass | ||
05/16/2023 | COT - LCEL - Electrical Above Ceiling | Passed | ||
11/12/2022 | COT - LCEL - Electrical Above Ceiling | Re-inspection required | this inspection is for above ceiling on second floor TI |