Inspection History Details
Inspection Status: Not Ready
Inspection History: COT - LCBU - Building Final
Permit Number - T22CM04242
Inspection Description - COT - LCBU - Building Final
Inspection Status - Not Ready
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/27/2022 | COT - LCBU - Building Final | Not Ready | ||
04/11/2023 | COT - LCBU - Building Final | Re-inspection required | Complete all doors per plan, fire dept has not signed off, Restroom sink is ADA non-compliant, no access to exhaust fan on roof. | |
04/12/2023 | COT - LCBU - Building Final | Re-inspection required | Complete all doors per plan, fire dept has not signed off, Restroom sink is ADA non-compliant, no access to exhaust fan on roof. 4/12/23: rooftop outlet required to be WR, doors not installed, Fire Dept has not signed off |
|
04/13/2023 | COT - LCBU - Building Final | Partial Pass | Complete all doors per plan, fire dept has not signed off, Restroom sink is ADA non-compliant, no access to exhaust fan on roof.Complete all doors per plan, fire dept has not signed off, Restroom sink is ADA non-compliant, no access to exhaust fan on roof. 4/12/23: rooftop outlet required to be WR, doors not installed, Fire Dept has not signed off. 4/13/23: OK to issue a Temporary Certificate of Occupancy Level 4 |
|
05/16/2023 | COT - LCBU - Building Final | Passed |