Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Not Ready
Inspection History: COT - RSPL - Plumbing Final
Permit Number - T22CM03919
Inspection Description - COT - RSPL - Plumbing Final
Inspection Status - Not Ready
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/27/2022 | COT - RSPL - Plumbing Final | Not Ready | ||
| 06/15/2022 | COT - RSPL - Plumbing Final | TLUNDBERG | Denied | Entered by VVERA1 - DE 1. Disconnect gas line from meter. Only SWG can connect new lines to their meter. 2. Rocky soil conditions, place enough sand on site to cover gas line a minimum of 12” after it passes inspection 3. CSST can not be used under ground. |