Permit: T22CM03902

Parcel: 110113750


Addresses:

4857 E GRANT RD


Inspection Status: Re-inspection required

Inspection History: COT - HCBU - Building Final 

Permit Number - T22CM03902

Inspection Description - COT - HCBU - Building Final 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
07/28/2023 COT - HCBU - Building Final  Re-inspection required 7/28/23: okay for TCO Level 4
1. Remove all construction debris from the roof, replace missing insulation on line sets, wrap all insulation with UV resistant tape, install anti-thief spinners on Freon ports, pipe overflow water from MAU to roof drains. 2. Toilet is past the 16 to 18" requirements. 3. 3-compartment sink require all sinks to drain independently to floor drain.
07/31/2023 COT - HCBU - Building Final  Re-inspection required 7/28/23: 1. Remove all construction debris from the roof, replace missing insulation on line sets, wrap all insulation with UV resistant tape, install anti-thief spinners on Freon ports, pipe overflow water from MAU to roof drains. 2. Toilet is past the 16 to 18" requirements. 3. 3-compartment sink require all sinks to drain independently to floor drain.

7/31/23: drain from MAU to roof drains is not code compliant and is leaking, toilet in south restroom is ADA non-compliant.
11/02/2023 COT - HCBU - Building Final  Passed