Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Not Ready
Inspection History: COT - FCON - Fire - Final
Permit Number - T22CM03725
Inspection Description - COT - FCON - Fire - Final
Inspection Status - Not Ready
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
COT - FCON - Fire - Final | Not Ready | |||
COT - FCON - Fire - Final | Not Ready | |||
COT - FCON - Fire - Final | Not Ready | |||
COT - FCON - Fire - Final | Not Ready | |||
COT - FCON - Fire - Final | Not Ready | |||
07/16/2024 | COT - FCON - Fire - Final | Partial Pass | Water flow, Tamper, Backflow, Elevator Report, Exposed wires in corridor, Concealed sprinkler covers painted to ceiling, painted heads in 7408 | |
08/02/2024 | COT - FCON - Fire - Final | Partial Pass | This property has been placed on fire watch. OK for TCO level 4 Building #7 units 7401, 7402, 7403, 7404, 7405, 7406 only. | |
08/15/2024 | COT - FCON - Fire - Final | Partial Pass | 4th floor units approved, still need smoke detectors in boiler room and storage closet and CO detector in boiler room on 4th floor. Ok for TCO level 4 units 7407-7413. Property remains on fire watch. | |
08/16/2024 | COT - FCON - Fire - Final | Partial Pass | This property is still on fire watch and will be until completed. OK to obtain a TCO level 4 for the 3rd floor. | |
09/10/2024 | COT - FCON - Fire - Final | Partial Pass | North/East exit door does not latch when closed, Smoke detectors need to be added to the storage rooms on the 2nd floor, Sprinkler final for 2nd floor still needs to be done. | |
07/17/2024 | COT - FCON - Fire - Final | Re-inspection required | Fire alarm repaired, 4th floor elevator lobby exit sign out, light blocking sprinkler head needs to be removed, painted heads in tenant spaces, east stairwell EM lights out, west stairwell old EM lights removed or working. Elevator report. | |
06/28/2024 | COT - FCON - Fire - Final | Re-inspection required (with fee) | ||
COT - FCON - Fire - Final | Not Ready | I could not get in touch with the contracter. | ||
10/03/2024 | COT - FCON - Fire - Final | Partial Pass | Old not in use fire alarm equipment needs to be removed. Knox box for building 8 to access FACP, FACP sign |