Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T22CM03375

Parcel: 141024760


Addresses:

9715 E SANDAL TR


Inspection Status: Not Ready

Inspection History: COT - RSEL - Electrical Final 

Permit Number - T22CM03375

Inspection Description - COT - RSEL - Electrical Final 

Inspection Status - Not Ready

Date Description Inspector Results Comments
10/27/2022 COT - RSEL - Electrical Final  Not Ready
06/09/2023 COT - RSEL - Electrical Final  Re-inspection required electrical not ready
06/28/2023 COT - RSEL - Electrical Final  Passed