Permit: T22CM03346

Parcel: 141202500

Inspection Status: Not Ready

Inspection History: COT - RSEL - Electrical Final 

Permit Number - T22CM03346

Inspection Description - COT - RSEL - Electrical Final 

Inspection Status - Not Ready

Date Description Inspector Results Comments
10/27/2022 COT - RSEL - Electrical Final  Not Ready
09/08/2022 COT - RSEL - Electrical Final  TGAUSP Denied Entered by NGARCIA3 - Denied, plans call for 225A max rating on panel, 50A back-feed too much for existing conditions
05/23/2023 COT - RSEL - Electrical Final  Re-inspection required
06/09/2023 COT - RSEL - Electrical Final  Passed Approved, DGC Clearance to TEP is required for the solar meter