Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T22CM02842
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/10/2022 | PLUMBING - FINAL | Approved | Approved | |
10/06/2022 | PLUMBING - FINAL | Partial Approval | Partial. Ground generators, 90 degree angle needed on condensate line, missing post tent ion tag. Missing tempered glass in bathroom. Adjust dishwasher hose. Need cut sheets for condenser units. | |
10/03/2022 | PLUMBING - FINAL | Not ready for Inspection | Not ready | |
05/20/2022 | PLUMBING - FINAL | Correction Required | Corrections required, Gray water installed at rough soil but will require revision to reflect as built prior to final inspection. | |
04/18/2022 | PLUMBING - FINAL | Prior to Final Inspectn | NO FINAL UNTIL THE PUBLIC SEWER G-2020-101/P21WP00064 (LA ESTANCIA DE TUCSON - PHASE II - OFFSITE 4) IS ACCEPTED AND RELEASED BY PCRWRD AND NO FINAL UNTIL THE PUBLIC SEWER G-2020-090/P21WP0062 (LA ESTANCIA DE TUCSON - PHASE II - PARCEL 5) IS ACCEPTED AND RELEASED BY PCRWRD |