Inspection History Details
Inspection Status: Not Ready
Inspection History: COT - RSEL - Electrical Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/27/2022 | COT - RSEL - Electrical Final | Not Ready | ||
| 09/12/2023 | COT - RSEL - Electrical Final | Re-inspection required | 9/12/23:AC unit breaker requires 45-50Amp, AC unit disconnect fuses min 45Amp, Secure and seal all roof jacks. | |
| 09/14/2023 | COT - RSEL - Electrical Final | Passed | 9/12/23:AC unit breaker requires 45-50Amp, AC unit disconnect fuses min 45Amp, Secure and seal all roof jacks. 9/14/23: Level 4 TCO |