Inspection Status: Passed
Inspection History: COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.
| Date |
Description |
Inspector |
Results |
Comments |
| 08/04/2022 |
COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. |
TLUNDBERG |
Approved |
Entered by NGARCIA3 - AP |
| 08/02/2022 |
COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. |
TLUNDBERG |
Denied |
Entered by NGARCIA3 - E
1. Connect duct to air handler
2. Connect line-set
3. Maintain min 10 feet between fresh air intake and vent
4. Move smoke det 3 feet from bathroom opening
5. Shim & strap 4-point bearing trusses |