Permit: T22CM01823

Parcel: 141432810


Addresses:

6712 E VIA OLMEDA


Inspection Status: Passed

Inspection History: COT - RSBU - Exterior Clips/Sheathing 

Permit Number - T22CM01823

Inspection Description - COT - RSBU - Exterior Clips/Sheathing 

Inspection Status - Passed

Date Description Inspector Results Comments
08/15/2022 COT - RSBU - Exterior Clips/Sheathing  SCARRAZCO Approved Entered by VVERA1 - approved
06/17/2022 COT - RSBU - Exterior Clips/Sheathing  TLUNDBERG Partial Approval Entered by NGARCIA3 - PA Interior shear walls are missing all anchors, approximately 12 MASA are incorrectly set. All new anchor bolt substitutes SHALL be Titan, as City Inspectors can not determine the embedment length of wedge anchors.