Permit: T22CM01767

Parcel: 134260120


Addresses:

518 S MANN AV

Inspection Status: Not Ready

Inspection History: COT - LCBU - Framing

Date Description Inspector Results Comments
10/27/2022 COT - LCBU - Framing Not Ready
09/15/2022 COT - LCBU - Framing RCHANDLER Denied Entered by NGARCIA3 - Denied: Corrections not completed.
09/12/2022 COT - LCBU - Framing RCHANDLER Denied Entered by NGARCIA3 - -Denied. 1-Install fire blocking per Code. 2-Install Exhaust fan ducts and terminations. 3-Install smoke detector outside of separated bedroom. 4-Install nail protection at furring strips. 5-Obtain approved revision for two beams at former bearing walls to verify sizing is sufficient to carry loads.
02/06/2023 COT - LCBU - Framing Re-inspection required
02/27/2023 COT - LCBU - Framing Passed Corrections completed, except for still no approved plans on site.
04/27/2023 COT - LCBU - Framing Canceled
05/01/2023 COT - LCBU - Framing Passed