Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/06/2023 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | Re-inspection required | 1. approved plans not on site 2. block all register boxes 3. fire block all penetrations in furr down and top plate 4. move smoke det 3 feet from register and bathroom opening 5. remove all foam at CMU wall openings, grout sides and lintels. Wood cannot support masonry. 6. all wood in contact with the floor is required to be termite treated. 7. fill vents thru the roof with water 8. daylight the laundry room exhaust fan 9. remove & replace all elect boxes attached to framing with drywall screws inside the box. |
|
| 02/27/2023 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | Passed | Corrections completed, except for still no approved plans on site. | |
| 04/27/2023 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | Canceled | ||
| 05/01/2023 | COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. | Passed |