Inspection History Details
Inspection Status: Not Ready
Inspection History: COT - RSEL - Service Upgrade
Permit Number - T22CM01585
Inspection Description - COT - RSEL - Service Upgrade
Inspection Status - Not Ready
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/26/2022 | COT - RSEL - Service Upgrade | Not Ready | ||
| 06/13/2022 | COT - RSEL - Service Upgrade | DQUINN | Denied | Entered by VVERA1 - de 1. Have TEP inspect their line from the trans to pedestal, for backfilling approval. 2. Move interior sub panel, which is intended to be upgraded, out of the closet to an acceptable interior location or the exterior of the house. 3. Install raised letter metal address tag to main panel cover. 4. Install gas and water bonding. Then recall for 2065 inspection. |
| COT - RSEL - Service Upgrade | Passed |