Inspection Status: Not Ready
Inspection History: COT - RSEL - Electrical Final
| Date |
Description |
Inspector |
Results |
Comments |
| 10/27/2022 |
COT - RSEL - Electrical Final |
|
Not Ready |
|
| 08/07/2023 |
COT - RSEL - Electrical Final |
|
Canceled |
|
| 12/06/2023 |
COT - RSEL - Electrical Final |
|
Re-inspection required |
12/6/23: GFCI all outlets within 6 l/f of utility sink, water heater T&P line is required to terminate to the exterior, label all breakers in sub-panel, install a lock out on water heater breaker |
| 12/20/2023 |
COT - RSEL - Electrical Final |
|
Passed |
12/20/23: GFCI outlets have been installed within 6' of any water source. Water heater T & P valve has been routed to the exterior of house. Electrical panel is properly labeled. A disconnect has been installed in water heater closet in place of the breaker lockout. Project is complete. Okay to issue Certificate of Occupancy for project. |