Inspection History Details
Inspection Status: Not Ready
Inspection History: COT - LCBU - Building Progress
Permit Number - T22CM00954
Inspection Description - COT - LCBU - Building Progress
Inspection Status - Not Ready
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/26/2022 | COT - LCBU - Building Progress | Not Ready | ||
07/28/2022 | COT - LCBU - Building Progress | TGAUSP | Partial Approval | Entered by NGARCIA3 - Partial, windows and bars in place |
11/03/2022 | COT - LCBU - Building Progress | Partial Pass | All units on this permit need line sets secured, 15 amp max breakers on condensing units, toilets and sinks caulked in, blanks in any open spaces in sub panels, unit 2 has 3 outlets not working, m/c cable secured with strain relief and routed properly, and suggest a shelf be put over water heater. | |
11/23/2022 | COT - LCBU - Building Progress | Passed |