Permit: T22CM00359

Parcel: 133553310


Addresses:

250 S VOZACK LN


Inspection Status: Not Ready

Inspection History: COT - HCBU - Interior Shear Bracing 

Permit Number - T22CM00359

Inspection Description - COT - HCBU - Interior Shear Bracing 

Inspection Status - Not Ready

Date Description Inspector Results Comments
10/26/2022 COT - HCBU - Interior Shear Bracing  Not Ready
03/20/2023 COT - HCBU - Interior Shear Bracing  Not Ready
04/18/2023 COT - HCBU - Interior Shear Bracing  Not Ready
04/24/2023 COT - HCBU - Interior Shear Bracing  Not Ready
04/26/2023 COT - HCBU - Interior Shear Bracing  Not Ready
05/22/2023 COT - HCBU - Interior Shear Bracing  Re-inspection required 5/22/23: maintain 3/8" min away from edge of gypboard with fasteners. The fastening schedule is 8" on edge and 12" field, do not tear the edge of the board.
05/23/2023 COT - HCBU - Interior Shear Bracing  Partial Pass 5-23-23: Southwest wing.
06/01/2023 COT - HCBU - Interior Shear Bracing  Partial Pass
06/12/2023 COT - HCBU - Interior Shear Bracing  Partial Pass 5/22/23: maintain 3/8" min away from edge of gypboard with fasteners. The fastening schedule is 8" on edge and 12" field, do not tear the edge of the board.

5-23-23: Southwest wing.

6/1/23: art studio, laundry, lounge, theater, east hall and rooms south of hall entire southeast wing okay to apply second layer of 5/8" gyp board

6/12/23: Main entrance lobby and all rooms in the northeast area approved to tape/texture.
12/22/2023 COT - HCBU - Interior Shear Bracing  Passed