Inspection Status: Approved
Inspection History: RESIDENTIAL INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 06/15/2022 |
RESIDENTIAL INTERMEDIATE |
|
Approved |
Approved |
| 06/10/2022 |
RESIDENTIAL INTERMEDIATE |
|
Denied |
De. 1-Seal all fire blocks in. 2-Wiring is not connected in walls. 3-Receptacle is buried in wall. 4-Install nail plates where piping or wiring is within 1-1/4” of edge of studs and plates. 5-Exhaust fan is not connected to electrical system. 6-Ground all metal boxes. 7-Block supply boxes at three sides 8- Alarm box and LB are not accessible in current location. 9 Protect dryer duct at top plate. 10-Separate neutrals from grounds at sub-panel. |
| 06/08/2022 |
RESIDENTIAL INTERMEDIATE |
|
Not ready for Inspection |
NR |