Inspection Status: Not Ready
Inspection History: Pool/Spa - Electric
| Date |
Description |
Inspector |
Results |
Comments |
| 10/03/2022 |
Pool/Spa - Electric |
SCARRAZCO |
Not ready for Inspection |
Entered by VVERA1 - Not ready. Missing light fixture in spa area. Light fixture in lagoon area needs to be 18” below the top of the rebar. |
| 10/26/2022 |
Pool/Spa - Electric |
|
Not Ready |
|
| 02/09/2023 |
Pool/Spa - Electric |
|
Re-inspection required |
30 amp breaker needed at sub panel that’s gfi protected |
| 02/17/2023 |
Pool/Spa - Electric |
|
Re-inspection required |
correct size breaker needed at sub panel or main panel that is gfi protected |
| 03/24/2023 |
Pool/Spa - Electric |
|
Re-inspection required |
at site, no one home. |
| 03/30/2023 |
Pool/Spa - Electric |
|
Re-inspection required (with fee) |
GFI protected breaker needed at sub panel or main breaker panel for pool pump |
| 04/14/2023 |
Pool/Spa - Electric |
|
Passed |
pool electrical is complete. |